Preamble
This application note is a continuation of Dataforth’s
Application Note AN109, which contains AC system
definitions and basic rules for calculations with examples.
The reader is encouraged to review AN109, References 3,
4, and 5 as background for this Application Note.
The Three-Phase Voltage System
Three-phase voltage systems are composed of three
sinusoidal voltages of equal magnitude, equal frequency
and separated by 120 degrees.
Figure 1 illustrates real-time cosine functionality and
associated phasor notation for a 3-phase line-to-line
voltage system with line voltage V12 as reference.
Review of Three-Phase Voltage System Properties
Three-phase supply voltages and load systems have two
basic configurations; the 4-wire “wye” and the 3-wire
“delta”. Figure 2 illustrates a basic 3-phase 4-wire wye
configured voltage system with V1N as reference and
Figure 3 shows a 3-wire delta configured voltage system
with V12 as reference respectively.
Important definitions, conventions, and calculation rules
for both the 3-phase 4-wire wye and the 3-wire delta
configured voltage systems are itemized in the following
list with the “messy” vector math omitted.
Phasor Orientation:
By definition, all sinusoidal phasors rotate in the
counterclockwise direction with a {1-2-3} or {3-2-1}
sequence and angles are measured as positive in the
counterclockwise direction. A 4-wire 3-phase wye system
is shown in Figure 2 with V1N chosen as reference. The
line-to-line voltages are V12, V23, and V32 with the lineto-
neutral voltages shown as V1N, V2N, and V3N. Figure
3 shows the proper line-to-line phasor voltages for a 3-
phase 3-wire delta configuration with V12 phasor chosen
as reference. Note: Any phasor can be chosen as
reference, the choice is completely arbitrary.
Phase Sequence:
A phase sequence defines the sequential timing by which
each line voltage phasor lags each other line voltage
phasor in the counterclockwise direction. Figures 1, 2 and
3 show a {1-2-3} phase sequence. A {1-2-3} sequence
means that V12 leads V23 by 120 degrees and V23 leads
V31 by 120 degrees. In addition, V1N leads V2N by 120
degrees and V2N leads V3N by 120 degrees. It is
necessary to establish the phase sequence before making
any calculations in order that calculated vector phasor
angles can becorrectly located relative to each other.
There are only two valid phase sequences; the {1-2-3}
sequence and the {3-2-1} sequence. Both these phase
sequences are determined by how the 3-phase transformer
supply lines (L1, L2, L3) are connected and labeled.
Figure 4 illustrates the
{3-2-1} sequence relative to the
{1-2-3} sequence. Note: The phase sequence can be
changed by simply reversing the connections of any two
of the three (L1, L2, L3) supply lines; however, this
should only be done in accordance with all the proper
codes, regulations, and approval of the plant engineering
staff.
Subscripts:
Maintaining the proper subscript order for all phasor
quantities is one of the most important keys to successful
3-phase calculations. Figure 4 shows the proper subscript
order for each of the two different phase sequences. For
sequence {1-2-3}, the proper order of subscripts is [12],
[23], and [31]; whereas, the proper subscript order for
sequence
{3-2-1} is [32], [21], and [13].
Subscript Notation:
Once the phase sequence is determined and the proper
subscripts are identified, calculations using these
subscripts together with the conventions adopted for the
AC version of Ohm’s Law will prevent angle errors.
By convention, V12 is the phasor voltage drop plus (1) to
minus (2) in the direction of current flowing from point
(1) toward point (2) and is equal to this current multiplied
by the AC impedance between points (1) and (2). For
example in phasor notation;
Phasor Addition/Subtraction:
Proper subscript notation establishes the correct method
for vector addition/subtraction of phasors. In Figure 2 the
line-to-line voltage phasors in this 3-phase {1-2-3}
sequence 4-wire wye system are composed of line-toneutral
phasor voltages as follows;
If the RMS line-to-neutral voltages are all equal (standard
balanced system), then the above equations show that
all
line-to-line phasor supply voltages are line-to-neutral
voltages multiplied by 3 and lead the line-to-neutral
voltage phasors by 30 degrees. For example, a standard
4-wire 3-phase wye system with line-to-neutral voltages
of 120 volts and V1N chosen as the reference phasor at
zero degrees has line-to-line voltages of;
V12 = 208∠ 30°; V23 = 208∠ -90°; V31 = 208∠ 150° .
Important concept: A 3-phase 3-wire delta configured
system of balanced voltages does not actually have lineto-
neutral voltages like the wye system. However, the
delta line-to-line voltages as shown in Figure 3 can still be
constructed from a theoretical set of balanced 3-phase
line-to-neutral voltages as illustrated above. The
relationships with these theoretical voltages are extremely
useful in locating delta phasor angles.
Calculation Procedures, Guidelines, and Formulae
The following list of procedures, guidelines and formulae
illustrate an outline of how to calculate 3-phase phasor
quantities using typical nameplate data taken from
individual load units.
Calculations proceed as follows;
- Identity the phase sequence; {1-2-3} or {3-2-1}
- Identify subscripts; [12], [23], [31] or [32], [21], [13]
- Assume L1, L2, L3 line currents flow toward loads
and neutral (return) current flows toward supply.
- Load current flows and voltage drops must follow the
subscript notations as previously defined.
- Use “Ohm’s Law for AC” to calculate magnitudes
and angles of each individual single-phase load
current. Review Dataforth’s AN109, Reference 1.
- Important concepts: Line currents for both wye and
delta balanced 3-phase loads are calculated using the
following relationships;
- AC input power = 3 x (Vline) x (Iline) x PF
- PF is the cosine of the angle by which line
currents lead or lag the line-to-neutral voltage.
Three-phase line-to-neutral voltages actually
exist in wye configurations; whereas, they are
theoretical in delta configurations. For example,
assume any balance 3-phase load with 10 amps
of line current and a PF of 0.866 (30° ) lagging. If
system sequence is {1-2-3} and V12 is reference,
then I1=10∠ -60°; I2=10∠ 180°; I3=10∠ 60° .
- Determine the power triangle quantities; watts “P”
and VARs “Q” for each load. Review Reference 1.
- Sum the previously calculated individual load
currents using proper subscript notation to determine
each individual line current
- Finally, sum all the individual load power triangle
quantities (Watts “P” and VARs “Q”) to establish the
system power triangle quantities; P, Q, and PF. It
this final step that establishes how a system’s load
population behaves.
Calculation Examples
The following examples assume a typical 208-120 volt
three-phase 4- wye configuration with a phase sequence
of {1 2 3}, and V12 chosen as reference. This is a wye
system; however, loads connected between each of the
three individual supply lines (L1, L2, L3) constitute a
208-volt 3-wire delta configuration. Three categories of
single-phase loads are assumed for the following
calculations. These categories are identical to those
defined in Application Note AN109 (Reference 1) and
listed below with the required nameplate data.
- Output Kilowatts; KW, Efficiency (optional), PF= 1
- Output Horsepower; HP, Efficiency, P
- Input KVA; KVA, PF, Efficiency is 100%.
Table 1 shows calculated values for an assumed
population of these loads. Readers should verify these
calculations. Dataforth offers an interactive Excel
workbook similar to Table 1, which automatically
calculates all the 3-phase system quantities. See
Reference 2 to download down load this Excel file.
Example Calculations for Line-to-Neutral Loads
Three-phase wye systems with neutrals can have equal or
unequal individual single-phase loads connected between
any of the supply lines (L1, L2, L3) and neutral. Systems
are balanced if all line-to-neutral loads are identical.
Figure 5 shows three groups of single-phase line-toneutral
loads connected on a three-phase wye system.
This configuration of single-phase loads can be
considered as a composite unbalanced wye load
Figure 6 shows three groups of single-phase line-to-line
loads connected on a three-phase wye system. This
configuration of single-phase loads can be considered as a
composite unbalanced delta load
Figure7 shows a group of balanced wye loads and a group
of balanced delta loads both of which are (can be)
connected on a three-phase wye system.
Table 1 is a composite set of calculated results for the
configurations shown in Figures 5, 6, and 7. These
calculations assume an arbitrary population of the type
loads previously defined and employ all the rules, procedures, and definitions as illustrated above. The
system results from Table 1 calculations are shown below
in Tables 2 and 3.
Line voltage V12 (208 at zero degrees) is reference for
the above current angles.
Readers are encouraged to verify these calculations.
As mentioned above, Dataforth provides an interactive
Excel file designed to assist the enthusiastic investigator
in calculating system currents and associated power
levels. This file allows an investigator to enter nameplate
data for all the system loads; whereupon, all line current
phasors and power quantities are automatically calculated.
Dataforth’s “Excel Interactive Work Book for Three-
Phase AC Calculations” can be downloaded from
Dataforth’s web site, see Reference 2 .
Figure 8 is an illustration of Dataforth’s Isolated True
RMS Input Module, SCM5B33. This function is also
available in a DIN rail package; the DSCA33. Dataforth
has a collection of signal conditioning modules designed
specifically for measuring AC RMS high-voltage
parameters using built-in attenuation. The reader is
encouraged to visit References 1, 6, 7, and 8.
Dataforth References
The reader is encouraged to visit Dataforth’s web site and
explore their complete line of isolated signal conditioning
modules and related application notes, see references
shown below.
- Dataforth Corp., http://www.dataforth.com
- Dataforth Corp., AN110 Excel
Interactive Work
Book for Three Phase AC Calculations
- Dataforth Corp., Application Note AN109,
Single Phase AC Measurements
- Dataforth Corp., AN109 Excel
Interactive Work
Book for Single Phase AC Calculations
- National Electric Code controlled by National Fire
Protection Agency, NFPA
- Dataforth Corp., SCMVAS Voltage Attenuator System,
- Dataforth Corp., SCM5B33 Series of Modular True RMS Signal Conditioners
- Dataforth Corp., DSCA33 Series of DIN Mount True RMS Signal Conditioners