Preamble
A surge tank is placed between two processing units
(Figure 1) to absorb flow rate fluctuations coming from
the upstream process so that the flow rate to the
downstream process changes less rapidly. To do this, the
tank level has to go up and down. Consequently, the level
controller should not try to hold the level as close as
possible to its set point. The controller should simply keep
the surge tank’s level between its upper and lower limits,
and do this with the least possible amount of change to its
output.
Although there are other methods of controlling the surge
tank level, the level-averaging method is preferred by
most operators and engineers. This method minimizes
control valve movement during disturbances, keeps the
level between its limits, and brings the level back to set
point in the long term. This Application Note describes
how to tune surge tank level controls using the levelaveraging
method.
Applicable Process Types
The tuning method described below is intended for use
with surge tank levels (Figure 1).
Target Controller Algorithm
The tuning rule presented here is designed for use on a
noninteractive controller algorithm with its integral time
set in minutes, such as the one provided in the Dataforth
MAQ®20 system.
Tuning Procedure
To tune the controller for level-averaging control, the
residence time of the surge tank, the greatest expected
change in flow rate, and the maximum allowable
deviation from set point must be known.
Residence Time (tres)
The residence time is the time it will take the tank to drain
from 100% level to 0% level if there is no flow into the
tank and the outlet valve is 100% open. It can be
calculated by dividing the volume of the vessel between
0% and 100% of its level measurement span (V) by the
maximum flow rate with the outlet valve wide open
(Qmax).
tres = V / Qmax
The same unit of measure must be used for volume in V
and Qmax.
Qmax must be expressed in volume / minute
Change in Flow Rate (Δfmax)
The greatest expected change in flow rate should be
expressed as a percentage of maximum valve capacity. If
available, historical trends of the level control valve’s
position can be used to find the largest change the
controller output has made over a relatively short period
of time.
Maximum Deviation from Set Point (ΔLmax)
The maximum allowable deviation of level from its set
point should be specified as a percentage of the full span
of the level measurement.
Tuning Equations
Once the three quantities described above are available,
tuning settings can be calculated for the controller.
KC = 0.74 Δfmax / ΔLmax
TI = 4 tres / KC
TD = 0
Where:
KC is controller gain
TI is the integral time in minutes
TD is the derivative time
The typical response of a surge tank tuned with the levelaveraging
tuning rule is shown in Figure 2.
Conclusion
While the Ziegler-Nichols and most other tuning methods
for level controllers are not suitable for use on surge
tanks, using the level-averaging tuning rule will keep the
surge tank’s level between its upper and lower limits with
the least possible amount of change to the controller’s
output.